Turret extinguishing systems
Stationary fire protection
Technical data for electronically controlled turrets
RM15C
RM35C
RM80C
RM130C
Flow rate
600 ­ 2,000 l/min
1,500 ­ 4,750 l/min
3,000 ­ 9,500 l/min
5,000 ­ 15,000 l/min
Rotation range
360°
360°
360°
360°
Swivel range
-50° / +90°
-90° / +90°
-90° / +90°
-20° / +70°
Nozzle
O-stream nozzle
O-stream nozzle
O-stream nozzle
O-stream nozzle
Stream adjustment
Electrical adjustment for
Electrical adjustment for
Electrical adjustment for
Electrical adjustment for
ful jet/spray jet
full jet/spray jet
full jet/spray jet
full jet/spray jet
Dry powder nozzle
optional
optional
optional
optional
Throw ranges
Water: > 65 m
Water: 130 m
Foam: > 47 m
­
­
Foam: 90 m
(with foam branch pipe)
(with foam branch pipe)
ChemCore
optional
optional
optional
optional
Operating temperature
-40 °C / +85 °C
-20 °C / +70 °C
-20 °C / +70 °C
-20 °C / +70 °C
Technical data for manually controlled turrets
RM8M
RM24M
Flow rate
400 ­ 1,900 l/min
400 ­ 3,000 l/min
Rotation range
360° continuous
360° continuous
Swivel range
-55° / +80°
-50° / +80°
Nozzle
O-stream nozzle
O-stream nozzle
Stream adjustment
Manual, continuous
Manual, continuous
Output setting
Manual, stepped
Manual, stepped
Dry powder nozzle
optional
optional
Throw ranges
Water: 60 m
Water: 80 m, foam: 50 m
Operating temperature
-20 °C / +70 °C
-20 °C / +70 °C